This will be the final question in this Test Your Knowledge series for motor reliability. Scroll to the end to see the correct answer.
On the Power Results page, Voltage Imbalance is 0.5%, Current Imbalance is 12%, and Impedance Imbalance is 12%. Power Factors for the three phases are 0.92, 0.91, and 0.92. The motor is running at 90% load under steady state conditions. Which fault zone is most likely to be the cause of these results?
A. Power Quality
B. Power Circuit
C. Rotor
D. Stator
If you would like to learn more about electric motor reliability using PdMA Technologies click Training in the menu section above to see Web Based, In Person and On-Site training opportunities.
The correct answer is B. Power Circuit